Skip to main content

Connections

Relay Outputs

4 Latching Relays

Technical Specifications

Relay Outputs
  • Type:

    Latching Relays

  • Quantity:

    4

  • Range:

    220 Vdc / 250 Vac max.
    2A max, 60W / 62.5VA

  • Connectors:

    4 sets of screw terminals (3.5 mm)

Technical Specifications

Form A Relay Outputs

External Supply

The RIO xR3 comes equipped with two Form A (normally open) and two Form C (change-over) latching relays. Wire out the most appropriate type for your application.

Latching relays only need to be energized when switching. This dramatically lowers the amount of energy required to hold a particular state.

The RIO xR3 relays will continue to hold their state during power outages and reboot cycles.

  • I/Os

    2 Form A

  • Connectors

    2 x 5 position

  • Pluggable

    Yes

  • Type

    Screw Terminal

  • Pitch

    3.5mm

Form C relays feature the ability to automatically toggle between two ‘operating states’.

In the example shown, Fan1 runs when the relay is in the NC position.

Fan2 will run as soon as the relay switches to the NO position.

The Form C relays support the same wiring configuration used for the Form A relays shown above, by not using the NC terminal.

 

  • I/Os

    2 Form C

  • Connectors
    4 x 5 position
  • Pluggable
    Yes
  • Type
    Screw Terminal
  • Pitch
    3.5mm

Form C Relay Outputs

External Supply

Form C Relay Outputs

External Supply

Another application for the use of Form C relay outputs is to drive Tower Status Indicator Lights (sometimes simply referred to as Tower Lights).

In the example shown, the  Green Light turns on when the relay is in the NC position.

The Orange Light will turn on as soon as the relay switches to the NO position.

 

  • I/Os

    2 Form C

  • Connectors

    2 x 5 position

  • Pluggable

    Yes

  • Type

    Screw Terminal

  • Pitch

    3.5mm

The graph shows the maximum load breaking capacity depending on the DC Voltage in use.

Mechanical endurance:  1 billion operations (typical).

Do not exceed the recommended application range.

Contact ratings as per UL:

  • 110 Vdc

    0.3 A – 33 W

  • 30 Vdc

    2.0 A – 60 W

  • 129 Vac

    0.5 A – 60 VA

  • 240 Vac

    0.25 A – 60 VA

  • 125 Vac

    1 A NO Side

  • 125 Vdc

    0.5 A NO Side

Maximum Load
Breaking Capacity

DC Voltages