Skip to main content

Connections

Hybrid Inputs

16 Analog or
Discrete Inputs

Technical Specifications

Hybrid Inputs
  • Type:

    Hybrid Inputs

  • Quantity:

    16, individually software configurable as
    DCI (discrete contact input) or analog input

  • Range:

    -60 Vdc to +60 Vdc

  • Resolution:

    1 mV

  • DCI Bias:

    24 Vdc

  • DCI Trigger:

    positive voltage,
    negative voltage or
    ground

  • Connectors:

    16 screw terminals (3.5 mm) + ground

Technical Specifications

Hybrid Inputs – DCI Mode

Internally Biased

Simply wire out your discrete contacts or alarm points to any of the 16 hybrid inputs.

Each input can be separately configured and programmed via software. Define individual high and low threshold levels.

Alarms can be triggered by a positive voltage, negative voltage, or ground.

  • I/Os
    16
  • Connectors
    4 x 5 position
  • Pluggable
    Yes
  • Type
    Screw Terminal
  • Pitch
    3.5mm

Measure any DC analog input in the range of +/- 60VDC. Hook your signals up to any of the 16 hybrid inputs, then define a whole set of thresholds in software to determine at what voltage level(s) alarms should be triggered (or not).

Supports converting an analog input voltage into arbitrary measurement units, user defined conversion formulas, escalating severity levels with flexible timing options.

  • I/Os
    16
  • Connectors
    4 x 5 position
  • Pluggable
    Yes
  • Type
    Screw Terminal
  • Pitch
    3.5mm

Hybrid Inputs – Analog Mode